Grid to GPU — NVIDIA 800 VDC architecture, one megawatt followed down

13.8 kV ACMedium voltage from the grid
DC power blockGrid to 800 V DC in one step
AI factory hallRoof removed
13.8 kV AC in
Solid-state transformersOCP LVDC SST specification, v0.3
800 V DC out
13.8 kV AC inMedium-voltage switchgear
Power cells in seriesOne string per phase · illustrative
Medium-frequency transformersIsolation in a fraction of the iron
800 V DC outCell outputs in parallel
800 V DC trunkFrom the power block
Row buswayOverhead, 800 V DC
Rack rowsLayout illustrative
Tap-off box
800 V sidecarPower and energy storage · illustrative
Kyber rack
Compute bladesFour chassis of 18 · illustrative
800 V inPOS · RTN · PE
One compute blade
64:1 LLC converter800 V → 12 V
Rubin Ultra package
Vera CPU
Cold platesLiquid cooled · illustrative
800 V DC in
Planar transformer
Power switches
12 V outCopper, short and thick
GPU diesLayout illustrative
HBM stacksCount illustrative
Voltage regulators12 V → core
Compute arraysFloorplan illustrative

Grid to GPU

One megawatt, from the edge of the site to a single die

Medium-voltage AC arrives at the fence. One conversion later it is 800 V DC, and it stays DC until the tray.

NVIDIA · May 2025 · NVIDIA · August 2026

DC Power Block

Medium-voltage AC in, 800 V DC out, in a single step

Solid-state transformers at the perimeter turn it straight into 800 V DC, so the racks no longer need AC power supplies.

NVIDIA · May 2025 · NVIDIA · August 2026

Solid-State Transformer

Power electronics where the line-frequency transformer used to be

In a typical design each phase is shared across a string of power cells. Every cell rectifies its slice, passes it through a small high-frequency transformer, and hands it to one 800 V DC bus.

NVIDIA · May 2025 · Layout illustrative

Why SSTs switch on silicon carbide →Wolfspeed · March 2026

Overhead 800 VDC Busway

One backbone for racks from 100 kW to beyond 1 MW

The busway runs above every row. Racks can grow without the hall being rebuilt.

NVIDIA · May 2025 · NVIDIA · August 2026

Tap-Off to the Rack

800 V drops from the busway into a sidecar beside the rack

At GTC 2025 NVIDIA showed an 800 V sidecar powering 576 Rubin Ultra GPUs in one Kyber rack.

NVIDIA · May 2025

Kyber

576 Rubin Ultra GPUs in a single rack

800 V enters on two conductors and a protective earth, and stays 800 V until it reaches the compute tray.

NVIDIA · May 2025 · NVIDIA · October 2025

One Compute Blade

800 V comes all the way to the tray

The big step down happens on the tray itself, next to the GPUs it feeds.

NVIDIA · October 2025 · Layout illustrative

64:1 LLC

800 V to 12 V in one step, in 26% less area

One resonant stage goes from 800 V to 12 V, where today's racks use a power supply and a second converter.

NVIDIA · October 2025

Rubin Ultra

12 V becomes core voltage right beside the package

A ring of voltage regulators makes the final conversion. From here the current is enormous, so the path is millimetres long.

NVIDIA · May 2025 · Layout illustrative

Where the Power Arrives

One of 576 GPUs, at the end of a single DC chain

Grid, one conversion, a busway, one more conversion on the tray, and the regulators. That is the whole path.

NVIDIA · May 2025 · NVIDIA · October 2025

Back to the Grid

Every watt on that die left the grid as 13.8 kV AC

Up to 5% more of it arrives, with 45% less copper on the way.

NVIDIA · May 2025

Scroll to follow the power
← sections

Further

Carbide: why the switches in a solid-state transformer are silicon carbide, and how switching faster shrinks the transformer

Sources

An independent illustration of NVIDIA's published 800 VDC design. Layouts marked illustrative are not NVIDIA's. Not affiliated with NVIDIA.

← sections
四宫格